Examples
Semiconductor Power Transformer
This 55 kVA power transformer supplies voltage to a semiconductor capitol equipment processing tool. This unit has a 480 volt primary with ±5% taps. The secondary is 15 volts line to line. The terminal strip used on the primary, as well as the copper bar tabs on the secondary, are both ring-lug compatible—an industry standard for the semiconductor industry.
Technical Specifications
Power Rating
55 kVA
No. of Phases
3
Frequency
50/60 Hz
Primary Voltages
456 Vrms
480 Vrms
504 Vrms
Secondary Voltages
15 Vrms L-L at 2,117 Arms
Options
Universal taps
Ring lug compatible
Custom mounting dimensions
X-Ray Distribution Transformer
This 15 kVA power transformer supplies power to a 3D x-ray microscope designed for research. This unit has universal taps set at 180, 200, 220, 240, 380, 400, 420, 440, and 480 volts. The secondary has four 208 volt outputs hooked up to receptacles for easy customer input. This unit is housed in a NEMA 1 enclosure and contains circuit protection for equipment and personnel safety.
Technical Specifications
Power Rating
15 kVA
No. of Phases
3
Frequency
50/60 Hz
Primary Voltages
180 Vrms
200 Vrms
220 Vrms
240 Vrms
380 Vrms
400 Vrms
420 Vrms
440 Vrms
480 Vrms
Secondary Voltages
208 Vrms @ 20 Arms
Options
Universal taps
Ring lug compatible
Receptacles for universal input
Circuit protection
Custom Power Transformer for Blood Analyzing Tools
This is a 2.3 kVA power transformer for supplying power to a blood analysis instrument. This unit has universal taps set at 100, 115, 127, 220, 230, and 240 volts. The secondary has three outputs at 110 volts at 230 amps, 115 volts at 20 amps, and 230 volts at 3 amps hooked up to a touch-safe barrier strip. This unit can handle 2 kilo-volts DC for one minute primary to core, 2 kilo-volts DC for one minute secondary to core, and 5 kilo-volts DC for one minute primary to secondary.
Technical Specifications
Power Rating
2.3 kVA
No. of Phases
1
Frequency
50/60 Hz
Primary Voltages
110 Vrms
115 Vrms
127 Vrms
220 Vrms
230 Vrms
240 Vrms
Secondary Voltages
100 Vrms @ 23 Arms
115 Vrms @ 20 Arms
230 Vrms @ 3 Arms
Options
Universal taps
Ring lug compatible
Safe-touch terminals
Heater-Vacuum Furnace Transformer
This 40 kVA power transformer supplies power to a heater vacuum furnace. This unit has primary taps set at 380, 400, and 415 volts line to line. The secondary has an output at 45 volts, 298 amps. This unit is terminated to a terminal board and silicon-bronze hardware.
Technical Specifications
Power Rating
40 kVA
No. of Phases
3
Frequency
50/60 Hz
Primary Voltages
380 Vrms L-L
400 Vrms L-L
415 Vrms L-L
Secondary Voltages
45 Vrms @ 298 Arms
Options
Ring lug compatible